Ventilation in day-care centres and sick leave among nursery children

Research output: Contribution to journalJournal articleResearchpeer-review

Several studies have reported poor indoor air quality (IAQ) in day-care centres (DCCs) and other studies have shown that children attending them have an increased risk of respiratory and gastrointestinal infections. The aim of this study was to investigate whether there is an association between ventilation in DCCs and sick leave among nursery children. Data on child sick leave within an 11 week period was obtained for 635 children attending 20 DCCs. Ventilation measurements included three proxies of ventilation: air exchange rate (ACR) measured with the decay method, ACR measured by the perfluorocarbon tracer gas (PFT) method, and CO2 concentration measured over a 1-week period. All but two DCCs had balanced mechanical ventilation system, which could explain the low CO2 levels measured. The mean concentration of CO2 was 643 ppm, exceeding 1000 ppm in only one DCC. A statistically significant inverse relationship between the number of sick days and ACR measured with the decay method was found for crude and adjusted analysis, with a 12% decrease in number of sick days per 1 h(-1) increase in ACR measured with the decay method. This study suggests a relationship between sick leave among nursery children and ventilation in DCCs, as measured with the decay method.

Original languageEnglish
JournalIndoor Air
Volume26
Issue number2
Pages (from-to)157-167
Number of pages11
ISSN0905-6947
DOIs
Publication statusPublished - Apr 2016